friendsoftheriverteign.orgLog in
Moretonhampstead STW, Moretonhampstd

Spill evidence · Friends of the River Teign

Moretonhampstead STW, Moretonhampstd

Storm overflow at the works · SBB00807 · feeds MORETONHAMPSTEAD_STW_MORETONHAMPSTEAD
Dry spill

Evidence strength

Medium confidence
  • Dry across a 3-day window
  • Rain gauge close (≤5 km)
  • Short discharge (<1 h) — weaker signal

The discharge

Spill day
Thursday, 9 April 2020
Started
9 Apr 2020, 07:01
Ended
9 Apr 2020, 07:23
Duration
22 minutes 30 seconds
Receiving water
Wray Brook
Parish
Moretonhampstead

Rainfall evidence

Daily rainfall at the matched gauge (Mardon Down) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Dry spill4-day window: Wet weather
DateRainfall
09/04/2020 (spill day)0 mmdry
08/04/20200 mmdry
07/04/20200 mmdry
06/04/20200 mmdry
05/04/20205.1 mmrain

River flow that day: 2.279 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 3.2 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Not Applicable
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB00807). Rainfall: EA Hydrology gauge 323b21d8-c9a4-4681-bc5c-62d7337993ac. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Teign Data.