friendsoftheriverteign.orgLog in
Summerhill pumping station, Ilsington

Spill evidence · Friends of the River Teign

Summerhill pumping station, Ilsington

Pumping station overflow · SBB01191 · feeds HEATHFIELD STW
Dry spill

Evidence strength

Medium confidence
  • Sustained discharge (≥1 h)
  • Dry on the EA 1-day window
  • Rain gauge close (≤5 km)
  • Monitor 92% operational that year

The discharge

Spill day
Thursday, 25 April 2024
Started
25 Apr 2024, 10:46
Ended
25 Apr 2024, 11:50
Duration
1 hour 4 minutes
Receiving water
Liverton Brook
Parish
Ilsington

Rainfall evidence

Daily rainfall at the matched gauge (Bickington) for the spill day and the days before. A spill is dry when every day in the window is ≤ 0.25 mm.

1-day window: Dry spill3-day window: Wet weather4-day window: Wet weather
DateRainfall
25/04/2024 (spill day)0.1 mmdry
24/04/20240 mmdry
23/04/20240 mmdry
22/04/20240.7 mmrain
21/04/20240 mmdry

River flow that day: 3.329 m³/s. Verify at the EA rainfall station.

Gauge proximity

Outlet (red) vs matched rain gauge (blue), 3.3 km apart. Closer means the rainfall reading is more representative of the overflow.

Loading map…

Severity & context

Bathing water
Not Applicable
Shellfish water
Teign Estuary
Ahead of the works
Yes — the treatment works' own overflow stayed shut that day, so capacity was available. Avoidable.
EA annual return (2024)
98 counted spills · 1482 h total
Monitor uptime (2024)
92% operational
Method & provenance. Dry/wet classification is decided by rainfall at the nearest EA gauge — ≤ 0.25 mm on the spill day and each preceding day of the window (how we classify). Spill data: Environment Agency EDM (outlet SBB01191). Rainfall: EA Hydrology gauge 31653dd5-c1ed-4091-a860-5e8d25936861. A dry spill is precautionary evidence of a likely fault, not proof of an offence — we test the rainfall, not the works' flow. Generated by River Teign Data.